Standard
Diffusion Transmitter The CSA approved LEL-1000 Combustible Detector Head is used in the detection of combustible gases. Its modern circuitry and reliable gas sensing element provide all that is required to allow the standard linear 4-20mA signal to be directly interfaced to any control unit capable of using this signal. The simplicity of installation, operation, durability of construction and the low cost make the LEL-1000 ideal for any applications. |
Specifications |
| APPROVALS | CSA APPROVED FILE #LR60959 |
| INPUT VOLTAGE | NOMINAL 24 VDC @ 0.150 AMPS MINIMUM 12 VDC @ 0.225 AMPS MAXIMUM 30 VDC @ 0.125 AMPS |
| OUTPUT SIGNAL | 4-20mA (NON-LATCHING) |
| ACCURACY | 5% OF FULL SCALE |
| REPEATABILITY | * 2% OF FULL SCALE |
| DRIFT | LESS THAN 3% PER MONTH |
| OPERATING TEMPERATURE | -40* C TO +75* C |
| HUMIDITY RANGE | 0 - 99% NON-CONDENSING |
| PRESSURE LIMITS | 600 - 900 MM HG |
| VELOCITY LIMITS | 0 - 1000 FT/M |
| MINIMUM OXYGEN CONTENT ** | 10% VOLUME |
| WIRING REQUIREMENTS: | SHIELDED WIRING IN CONDUIT 2. WIRE LOOP RESISTANCE UP TO 8 OHMS MAY BE USED. THIS APPLIES TO THE CURRENT CARRYING CONDUCTORS, TERMINALS 24 VDC AND COMMON. THE SIGNAL TERMINAL (F.B.) CAN BE CONNECTED USING RESISTANCE UP TO 1000 OHMS. |
Parts |